<%@LANGUAGE="JAVASCRIPT" CODEPAGE="936"%> Intelligent control strategy
Intelligent Control Strategy

 

All the procedures of sampling and monitoring will be controlled under the smart control system, which is being developed in our project. We have designed the control strategy for the treatment plant and smart laboratory system. The basic functions of the control strategy are listed in Table below.

 

NO
Routine Name
Function
1
MR
Main routine
2
INI
Close all valves, turn off pumps and motors in smart lab and sampling system, and initialize PLC status
3
ENGUNIT
Convert analog input into engineering unit
4
Fault_Check
Check signal errors
5
SM_V
Operate the valves of smart laboratory system
6
SA_V
Operate the valves of sampling system
7
PLANT_V
Operate the valves of treatment plant system
8
DATA_C
Titration control
9
SIMU_1
Titration simulation
10
TITRA_1
pH, and ORP titration
11
WASH_1
Washing central chamber
12
WASH_2
Washing ISE chamber
13
WASH_3
Washing HMs chamber
14
CC_PR
Preparation of the calibration of MF chamber
15
CALI_PH
pH and ORP calibration
16
ISE_PR
Preparation of the calibration of ISE chamber
17
CALI_ISE
Calibration of Fluoride, Sulfide, Cyanide, Chlorides sensors in ISE chamber
18
HMS_PR
Preparation of the calibration of HM chamber
19
CALI_HMS
Calibration of the measurement of Zn, Cu, Pb, Cd in HM chamber
20
SAMPLING
Logic of Sampling system
21
INT_WASH
Wash logic with user interruption
22
INT_CALI
Calibration logic with user interruption

 

[Top]

 